Fire Emergency Evacuation Broadcast Panel
The DHI-HY-1801 combines broadcast operation, emergency audio source management and a power amplifier in a fire emergency broadcasting system. Operators can use the front-panel LCD, keypad and handheld microphone to manage recorded announcements, live voice broadcasts and external audio sources.
- Dedicated EMER key for emergency broadcasting and a handheld microphone for live announcements.
- LCD and status indicators for operation, power and fault information.
- Fixed-voltage 120 VAC speaker output with 350 W rated output power.
What Each Front-Panel Control Does
The numbered illustration identifies five operating areas on the DHI-HY-1801. Match each number with the detailed operating notes below.
Handheld Microphone
The left-mounted microphone is for live voice broadcasts. Press and hold its talk button to speak; release the button to end microphone broadcasting. During an emergency broadcast, microphone speech can be recorded automatically.
Status Indicator LEDs
The panel visibly identifies Power On, Main Power, Backup Power, Fault, Automatic, Emergency and Silence. The Fault indicator and audible warning signal help operators identify abnormal conditions.
LCD Information Screen
Shows the standby interface and operation menus. If a fault persists, the screen can automatically display the corresponding fault information.
Keypad and Dedicated Controls
Includes labeled All On, EMER and Silence keys, navigation/confirmation keys, and context-dependent playback or menu controls. The EMER key opens or exits emergency radio; Silence mutes the audible fault warning.
MIC, AUX and USB Ports
MIC connects the handheld microphone; AUX accepts a 3.5 mm external audio cable; USB accepts a compatible USB 2.0 flash drive for supported MP3 playback or audio import operations.
Four Audio and Broadcast Modes
The panel supports emergency pre-recorded messages, operator voice announcements, USB audio and external AUX playback. These are different audio paths, not four independently addressed speaker zones.
EMER Radio
Press EMER or select emergency radio from the menu to play a configured emergency audio source. Record1 is the default source; Record2 can be selected and falls back to Record1 when empty.
MIC Radio
Press and hold the handheld microphone button and speak. Releasing the button stops microphone broadcast. Voice can be recorded automatically when used during emergency radio.
USB / MP3
Insert a compatible USB flash drive, then select MP3 in the menu. Use the keypad for track selection, play/pause and playback-level controls.
AUX Input
Connect an external audio device through the 3.5 mm AUX input and select AUX from the menu to broadcast the incoming signal.
Built for Supervised Emergency Broadcasting
Main & Backup Power Monitoring
Supervises the main power supply and standby power supply and reports detected faults through sound and light indications.
Speaker-Line Fault Detection
Monitors the constant-voltage broadcast output line for faults, helping the operator identify broadcast circuit abnormalities.
Overload Protection
Reduces output voltage during minor overloads and shuts off output in severe overload conditions.
Programmable Air Cooling
Intelligent, programmable fan cooling helps manage amplifier temperature during operation.
LCD Fault Information
The screen provides operating menus and fault information, complementing the visible indicators and audible warning.
Fire Alarm Linkage
Supports external control-system integration via a 24 V start signal. A protocol-conversion communication module is described in the manual; verify the specific implementation for each project.
A Broadcast Panel with Three Matching Speaker Models
The DHI-HY-1801 is the central broadcast panel. Together with the fire alarm control panel, linkage/output equipment and field speakers, it can form a fire emergency evacuation broadcast system. DHI-HY-1820, DHI-HY-1821 and DHI-HY-1822 are alternative speaker types for different mounting conditions, not three controller-expansion boards.

speaker image
Surface-mounted ceiling speaker
3 W · AC 120 V
speaker image
Ceiling-mounted speaker
3 W · AC 120 V
speaker image
Wall-mounted speaker
3 W · AC 120 VDHI-HY-1801 Specifications
| Model | DHI-HY-1801 |
|---|---|
| Product Type | Fire Emergency Evacuation Broadcast Panel |
| Main Power Supply | AC 220 V / 50 Hz (datasheet rating) |
| Speaker Output | 120 VAC constant-voltage output |
| Rated Output Current / Power | 2.92 A / 350 W |
| Recording Duration | 30 minutes total; circular recording retains the latest 30 minutes when full |
| Emergency Audio Clip | Up to 30 seconds for a configured emergency broadcast audio source (manual) |
| Signal-to-Noise Ratio | ≥ 70 dB |
| Dimensions | 318 × 245 × 127 mm |
| Operating Conditions | 0°C to +40°C; ≤ 95% RH (non-condensing) |
| Installation | Standing Cabinet / Wall-Mounted — verify mounting arrangement for the supplied version |