Isolator Module

The TX7230 Isolators Module is compatible with the TX7004 Analogue Intelligent Fire Alarm Control Panel, both produced by the same manufacturer, T&A, to avoid compatibility issues with addressable communication.

Brand:
Tanda UK
SKU:
TX7230
Certification:
CE, CPR, LPCB
Devices:
70

Short-Circuit Isolation for Addressable Fire Alarm Loops

When a short circuit occurs, TX7230 modules on either side of the fault isolate the affected section so devices elsewhere on the loop can continue operating. Once the fault is cleared, the modules automatically reconnect the isolated section.

  • EN 54-17:2005
  • Automatic reset
  • Up to 70 monitored devices

How the TX7230 Isolates a Short Circuit

See what happens to communication with the TX7004 when Detector B’s section develops a short circuit.

  • Detector AOnline · TX7004
  • Detector BOnline · TX7004Offline · Short
  • Detector COnline · TX7004
The moving dot shows communication back and forth between TX7004 and Detector C. The red arc illustrates continued communication with Detector C through an unaffected part of the loop.

Normal operation
Detectors A, B, and C are online with the TX7004.

Key Features

Automatic Reset

Reinstates the isolated section after the short circuit clears.

Device Monitoring

Supports a maximum of 70 monitored devices.

LED Status

The indicator gives a single blink in normal operation and stays on while active.

Loop Powered

Draws operating power directly from the addressable loop.

Fixed Mounting Base

The module clips into a surface-mounted base.

TX7004 Compatibility

Designed for use with the TX7004 analogue addressable fire alarm control panel.

Technical Specifications

Short-Circuit Isolator Standard
EN 54-17:2005
LPCB Reference
1330f/01
CPR Certificate
2831-CPR-F2795
Operating Voltage
24 V DC nominal (16–28 V DC)
Standby Current
0.15 mA
Alarm Current
1.8 mA
Protocol
T&A
Output Impedance
480 Ω
Dimensions
108 × 86 × 38 mm
Operating Temperature
−10 to +50 °C
Ingress Protection
IP30
Relative Humidity
0–95%, non-condensing

Mounting and Loop Connections

  1. Fit the base to a standard one-gang electrical back box.
  2. Connect the incoming and outgoing loop conductors using the manufacturer's wiring diagram.
  3. Align the module with the base and press it into place until it locks.

Refer to the TX7230 installation manual for the wiring diagram and commissioning instructions.

Terminal Identification

Z1
Signal In (+)
Z2
Signal In (−)
Z3
Signal Out (+)
Z4
Signal Out (−)

Request a TX7230 Project Quote

Send FireMarket your quantities, panel model, or project requirements. Our team can help you source the TX7230 and compatible addressable loop devices.

Listed LPCB / CE-CPR
Compliance EN54-17:2005
Power Rating  
Input Voltage 24VDC [16V to 28V]
Current Consumption Standby 0.15mA, Alarm: 1.8Ma
Maximum Open Voltage
(VSO MAX)
11V
Minimum Open
Voltage (VSO MIN)
8V
Maximum Close
Voltage (VSC MAX)
3V
Minimum Close
Voltage (VSC MIN)
1.4V
Maximum Continuous
Current (IC MAX)
500mA
Maximum Transient
Output Current (IS MAX)
5A
Maximum Leakage
Current (IL MAX)
2mA
Max closed
impedance (ZC MAX)
0.65 ohms
Protocol T&A
Number of monitored Max 70 Devices
Output Impedance 480 ohms
Indicator Status Normal: Single blink/Active:Steady-on
Material / Colour ABS / White Glossy finishing
Dimension / LWH 108 mm x 86 mm x38 mm
Weight 152g (with Base), 81g (withoutBase)
Ingress Protection Rating IP30
Humidity 0 to 95% Relative Humidity, Non condensing

PRODUCT & TECHNICAL SUPPORT

Isolator Module FAQs

Frequently asked questions about this product, configuration, compatibility and technical requirements.

01. What is the TX7230 addressable isolator module used for?

The TX7230 is a loop-powered short-circuit isolator designed to protect an addressable fire alarm loop by isolating a faulted section while allowing unaffected sections to continue operating.

02. Why is short-circuit isolation important on an addressable fire alarm loop?

A short circuit can interrupt communication and power within the affected section. The TX7230 isolates that section to help limit the impact of a single wiring fault on the rest of the loop.

03. Does the TX7230 automatically restore the isolated loop section?

Yes. The TX7230 continues monitoring the fault and automatically reinstates the isolated section after the short circuit has been cleared.

04. How many devices can the TX7230 monitor?

The TX7230 is specified to monitor up to 70 devices. The final device quantity and isolator placement must follow the approved loop design and applicable local requirements.

05. Which fire alarm control panel is confirmed as compatible with the TX7230?

The TX7230 is confirmed for use with the TX7004 Analogue Intelligent Fire Alarm Control Panel using the TANDA protocol. Compatibility with other control panels or brands must be confirmed before ordering.

06. Is the TX7230 compliant with EN 54-17?

The TX7230 is identified as compliant with EN 54-17:2005 for short-circuit isolators, with LPCB reference 1330f/01 and CPR certificate 2831-CPR-F2795. Current certificate status and project-market acceptance should be confirmed before ordering.

07. Does the TX7230 require a separate power supply?

No. The TX7230 is powered directly from the detection loop, reducing the need for separate local power wiring.

08. What is the operating voltage of the TX7230?

The TX7230 has a nominal operating voltage of 24 VDC and a specified operating range from 16 VDC to 28 VDC.

09. What is the current consumption of the TX7230?

The specified current consumption is 0.15 mA in standby and 1.8 mA when active.

10. What current and impedance limits apply to the TX7230?

The TX7230 has a maximum continuous current of 500 mA, a maximum transient output current of 5 A, a maximum leakage current of 2 mA, and a maximum closed impedance of 0.65 ohms.

11. What do the TX7230 LED indications mean?

A single blinking indication represents normal operation, while a steady-on indication shows that the isolator is active.

12. What are the dimensions and weight of the TX7230?

The TX7230 measures 108 × 86 × 38 mm. It weighs approximately 152 g with the base and 81 g without the base.

13. What environmental conditions are specified for the TX7230?

The TX7230 is specified for operation from -10°C to +50°C and at 0% to 95% relative humidity without condensation. Its enclosure rating is IP30.

14. How is the TX7230 mounted?

The TX7230 is designed for surface mounting with its fixed base. The base can be secured to a standard one-gang electrical back box using two M4 screws before the module is aligned and locked into place.

15. How are the loop terminals identified on the TX7230?

Z1 is Signal In positive, Z3 is Signal Out positive, Z2 is Signal In negative, and Z4 is Signal Out negative. Wiring must follow the approved system design and applicable local requirements.

16. Who should install and commission the TX7230?

Installation and commissioning should be performed by qualified or factory-trained personnel. The voltage ratings, wiring, system compatibility, approved design, and applicable local requirements must be checked before operation.

17. How often should the TX7230 be maintained?

Semi-annual maintenance is manufacturer guidance for the TX7230. The actual inspection, testing, and maintenance schedule must follow applicable local regulations, the approved system design, site conditions, and the approved maintenance plan.

18. How should the TX7230 be cleaned and serviced?

Clean the external surface with a damp cloth and do not attempt to repair the internal circuitry. Removal, testing, and replacement should be performed by qualified personnel, followed by verification of normal system operation.

19. What should be checked if the control panel reports a loop fault involving the TX7230?

Qualified personnel should check for incorrect wiring or a damaged electronic circuit. If the TX7230 is confirmed to be defective, it should be replaced rather than repaired at circuit level.

Free Preliminary System Drawings

Working on a project budget without a system layout? FireMarket provides free preliminary drawings to help you estimate equipment quantities and costs.

Request Free Preliminary Drawings

Related Products