Conventional Fire Alarm Control Panel Max 16 Zone

Overview

TXC7002/TXC7004/TXC7008/TXC7016 Conventional Fire Alarm Control Panel is designed in compliance with EN 54-2 and EN 54-4. It’s compatible with TXC7101 Conventional Smoke Detector by EN 54-7, TXC7111 Conventional Heat Detector by EN 54-5, TXC7141 Conventional Manual Call Point by EN 54-11 and TXC7301 Conventional Sounder Strobe designed by EN 54-3. Control functions of the panel are enabled by a key switch and programming functions are enabled by an internal switch. This series of panels are basically the same in application and operation, their differences are zones and sounder outputs. TXC7016 Conventional Fire Alarm Control Panel (called FACP for short) will be described as the example in the following sections.

Brand:
Tanda UK
SKU:
TXC7016
Certification:
CE, CPR, TUV
Capacity:
≤32 / zone
Zones:
16 Zones, 2 Zones, 4 Zones, 8 Zones
16-zones
16-zones
2-zones
2-zones
4-zones
4-zones
8-zones
8-zones

Conventional Fire Alarm Control Panel Features

1, Up to 16 zones can be detected, compatible with conventional detectors and manual call points. Each of the 16 zones can be individually configured as maximum 15 conventional detectors. The total number of detectors and manual call points in a zone shall not exceed 32.
2, Three sounder outputs, one alarm output, one fault output and one disable/supervisory output.
3, Able to report short and open circuits of zones, sounder outputs and alarm output.
4, Test and disable functions.
5, Programmable on manual call point connection, sound modes, sounder delay modes and output delay modes.
6, Three access levels settable via the key switch and the internal switch.
7, Providing external ports includes RESET, EVAC, SILENCE.
8, Designed with standby batteries and space provision for two sealed lead-acid batteries.

Technical Specifications

Input Voltage: 100V~230VAC(+10%-15%), 50/60Hz
Input Current: 1.2 A
Fuse: 250VAC, T2A in SPS
Recommended Wiring: 1.5mm2 or above shield cable, complying with local installation codes.
Note: External overcurrent protection device is required and should be installed near the
Operating Voltage:
 Minimum Operating Voltage: 21.5V
 Maximum Charging Current: 350mA
 Maximum Charging Voltage: 27.6V
 Battery Type: Sealed lead-acid battery
 Maximum Battery Charging Capacity: 2 batteries, 7Ah/12V.
Recommended Battery Manufacturer and Model: Yuasa NP7-12
 Maximum internal resistance of the batteries: 1Ω
 Standby current of batteries when fully load: 0.1A
 Maximum operating current of the batteries: 2.1A
Detection Zone:
The FACP provides maximum 16 zones; each can be individually configured with maximum 15
conventional detectors.
Output voltage: 18VDC~28VDC
 Standby current: less than 6mA (connecting with 15 conventional detectors)
 Alarm current: about 25mA
 End-of-line-resistor: 4.7kΩ
 Resistance range for fire alarm: 150Ω~1.5kΩ (normally 510Ω)
 Recommended wiring: 1.0mm2 or above shield cable, complying with local installation codes.  Recommended cable length: no longer than 1000m
Output Interface:
 Fault output
 Type: normally open/close contact output
 Contact capacity: 1A/24VDC
 Disable/supervisory output (defaulted disable output)
 Type: normally open/close contact output
 Contact capacity: 1A/24VDC
 Alarm output
 Type: voltage output, normally open/close contact output are available (defaulted voltage output)
Contact capacity: 1A/24VDC
 Output voltage: 18VDC~28VDC
 Output current: 300mA in alarm
 End-of-line-resistor: 4.7kΩ
 Sounder 1# output
 Type: voltage output, normally open/close contact output (defaulted voltage output)
 Contact capacity: 1A/24VDC
 Output voltage: 18VDC~28VDC
 Output current: 300mA in alarm
 End-of-line-resistor: 4.7kΩ
 Sounder 2#~3# output
 Type: voltage output
 Output voltage: 18VDC~28VDC
 Output current: 300mA in alarm
 End-of-line-resistor: 4.7kΩ
 Auxiliary Power Output
 Output voltage: 18VDC~28VDC
 Output current: 20mA in standby and maximum 500mA in alarm
 Recommended wiring: 1.0mm2 or above shield cable, complying with local installation codes.  Recommended cable length: no longer than 1000m
Input Interface (For future use)
 RESET/EVAC/SILENCE input
 Type: normally open contact input
 Recommended wiring: 1.0mm2 or above shield cable, complying with local installation codes.  Recommended cable length: no longer than 1000m
Installation and Storage
The FACP is applicable for indoor use below the elevation of 2000m. Overvoltage level is Class II and
pollution degree is 2.
Installation Environment
Temperature: -5℃~50℃, Relative humidity≤95%, non-condensing
Storage Environment: Temperature: -25℃~50℃, Relative humidity≤95%, non-condensing

Related Products

FAQs

Q. Do you provide system design services?

A. Customization may be available for selected products. Feasibility, minimum quantities, costs and lead times depend on the product type and specific requirements

A. Yes. Share your BOQ, drawings or product list with quantities and technical requirements. We can help identify suitable products and prepare a quotation.

A. Compatibility cannot be assumed. It depends on the specific system, communication protocol and device models. Please contact us to verify before ordering.

Yes. Send us the product name, model, specifications or a reference photo, and we will check available sourcing options.

Yes. Send us the product name, model, specifications or a reference photo, and we will check available sourcing options.