TX7222 Addressable Zone Monitor and Sounder Circuit Module
Connect conventional detection and notification circuits to a compatible TANDA addressable fire alarm system. The TX7222 reports conventional zone alarms to the panel and switches its conventional sounder circuit when commanded.
- Conventional zone
- Up to 32 conventional detectors on N/P
- Address allocation
- Two consecutive addresses
See the Signal Travel Through the Module
Choose a scenario to see which way the signal travels between a TX7004 control panel, the TX7222 and the conventional circuit.
A conventional zone alarm is reported via the TX7222 to the addressable panel.
Silent functional demonstration. Refer to the installation manual for terminal connections and circuit requirements.
Conventional Circuits on an Addressable Loop
Zone Monitoring
The N/P input monitors compatible conventional smoke or heat detectors and manual call points. The panel identifies the reporting module address.
Sounder Circuit
The S+/S− output serves compatible conventional sounder strobes. The manual shows this circuit with an end-of-line resistor and an external DC supply connected to the module.
Circuit Supervision
Enable Input Check with an end-of-line resistor to report open- and short-circuit faults. Output Check monitors the output voltage when enabled.
Two Consecutive Addresses
Reserve two consecutive addresses for each module. Use the TX7932 handheld programmer to configure addressing and circuit-check settings.
Plug-In Mounting
The module clips onto its terminal base, which mounts to a standard single-gang electrical back box.
Dedicated Beam Interface
The D+/D− 24 V DC control output is specified for the TX7130 beam detector. Use the TX7222 manual for the interface arrangement.
Specification Highlights
- Addressable loop supply
- 16–28 V DC, 24 V DC nominal
- External supply
- 20–28 V DC
- End-of-line resistor
- 5.1 kΩ / ¼ W
- Addressing
- TANDA · range 1–254
- Indicators
- Alarm, fault and activation
- Dimensions (L × W × H)
- 108 × 86 × 38 mm
- Enclosure
- IP30
- Operating temperature
- −10 °C to +50 °C
- Weight with / without base
- 162 g / 87 g