TX7002 Intelligent Addressable Fire Alarm Control Panel
The TX7002 is an analogue addressable, microprocessor-based fire alarm control panel for fire detection, alarm monitoring and programmable system control. Available in configurations of up to two addressable loops, it supports flexible system design and commissioning.
The panel combines a 7-inch TFT touchscreen with an operational keypad, event indication and integrated control functions for straightforward day-to-day operation.
Up to 2 Addressable Loops — 254 Devices per Loop
The TX7002 supervises up to two monitored detection loops using the T&A protocol. Each loop supports address values from 1 to 254, giving a theoretical maximum of 508 addresses across two loops.
TX7002 Front Panel Functions
The TX7002 front panel integrates a 7-inch TFT touchscreen, system status LEDs, dedicated control keys, navigation and numeric keypads, a key switch and 30 zone LED indicators for fire alarm monitoring and operation.
Addressable Detection, Alarm Notification & Control
The TX7002 supports compatible addressable detectors, manual call points, alarm devices and interface modules. Configurable cause-and-effect logic can coordinate outputs for specified fire-event scenarios.
Efficient Commissioning & Event Management
Automated enrollment, colour-coded loop mapping, address conflict analysis and programmable Command Builder functions support installation, testing and maintenance.
Device Enrollment
Enroll all connected addressable devices or register additional devices.
Loop Mapping
View device information and colour-coded loop status on screen.
Cause & Effect
Use Command Builder to program fire-event control scenarios.
System Testing
Perform zone tests and one-man tests with sounder On/Off options.
TX7002 Key Technical Specifications
Core system information for fire alarm control panel selection and project planning.
| System Type | Analogue Intelligent Addressable Fire Alarm Control Panel |
|---|---|
| Addressable Loops | Up to 2 loops |
| Address Range | 1–254 per loop (T&A protocol) |
| Loop Protection | Built-in 4kV surge protection |
| Recommended Loop Cable | Up to 1,000m, subject to specified cable and installation conditions |
| Panel Networking | CAN Bus; up to 512 nodes stated in system specification (verify network design limits) |
| Programmable Zones | Up to 3,000 |
| Programmable Groups | Up to 3,000 total (1,000 sounder; 2,000 common) |
| Event Memory | 1,000 fire events; 10,000 general events |
| Display | 7-inch TFT touchscreen |
| Indicators | 24 status LEDs; 30 zone indicators |
| Panel Printer | Built-in printer |
| Communication Ports | USB, RS485 serial, RS232 serial, Ethernet; CAN Bus panel networking |
| Programmable Relays | 4 changeover relay circuits (NO/NC selection) |
| Fixed Outputs | 2 monitored circuits: sounder and fire protection equipment (FPE) |
| Input Supply | 230VAC (+10% / -15%), 50Hz |
| Dimensions (H × W × D) | 460 × 440 × 165mm |
| Weight | 9.40kg |
| Operating Conditions | -5°C to +40°C; 0–95% RH, non-condensing |
| Standards | EN 54-2 / EN 54-4 |