TX7140
Addressable Manual Call Point
The TX7140 is a Type A indoor addressable manual call point with a resettable operating element and digital addressing for T&A fire alarm systems.
Press to Activate. Reset with the Supplied Key.
Resettable Press Element
Press the non-breakable glass operating element lightly by hand to raise a manual fire alarm. No hammer is required.
Steady Alarm LED
The front-mounted LED lights steadily on activation, making the operated call point easier to locate at the installation site.
Key Reset
After the fire condition has cleared, open the protected flap at the bottom of the unit and use the supplied reset tool to return the operating element to its normal position.
See How a Manual Alarm Reaches the Panel
On activation, the TX7140 sends an addressable alarm signal to the TX7004 Analogue Intelligent Fire Alarm Control Panel. Both devices are manufactured by T&A for use in the same addressable fire alarm system. The programmed device address helps identify which call point was activated.
TX7140 call point
Fire alarm control panel
Example device address 024
Ready to demonstrate manual activation.
Illustrative panel image and simulated status. Display wording and device addresses vary by system configuration.
Mounting and Accessories
For either mounting option, connect the alarm loop at the terminal base and clip the TX7140 call point onto it.
Recessed Mounting
Use a suitable recessed installation position with space for the wiring behind the call point.
Recessed position → Terminal base → TX7140
Surface Mounting
Use the optional TX7140-MB back box when the call point and wiring need to sit on the wall surface.
Wall → TX7140-MB → Terminal base → TX7140
Optional Accessories
TX7140-MB Surface Mounting Box
Fits behind the call point and provides space for cable entry and wiring on a surface-mounted installation.
TX7140-PFC Protective Flip Cover
Fits over the front of the call point to reduce accidental activation. Lift the cover before pressing the call point. The rear terminal base still provides mounting and loop connections.
Technical Specifications
- Loop voltage
- 24 V DC nominal (16–28 V DC)
- Current draw
- 0.6 mA standby · 1.8 mA alarm
- Protocol and address range
- T&A · 1–254
- Classification and ingress rating
- Type A indoor · IP43
- Dimensions (L × W × H)
- 89 × 93 × 35 mm
- Operating temperature
- −10°C to +55°C
EN 54-11:2001 + A1:2005 · LPCB 1330g/01 · CPR 2831-CPR-F2796. The certificates identify the indoor surface-mounted configuration.